GPS-GE

Applications & Specific Features

  • Oil supply to appliance by gravity feed, GPS unit must be higher than appliance(s).
  • Various GPS models available with different sizes of reservoir.
  • Standard unit has 2 outlets for 2 appliances, more outlet versions available to special order.
  • Suction lift 9m vertical or 200m horizontal. See performance curves (Datasheet).
  • Oil supply installations using ‘dead leg’ pipework. GPS unit does not need external controls.
  • Anti siphon valve or ‘normally closed’ solenoid valve required at the main oil tank when oil level in tank is above GPS level.
  • Special GPS models available with greater reservoir, for acting as power generator reservoir
  • Special GPS models available with larger flow, for high output or modulating burners

Technical Characteristics

  • Voltage free general alarm outlet.

  • Output to attach anti-siphon solenoid valve.

  • Oil leak collector tray with infrared detector.

  • Safety thermostat (40ºC) for temperature gasification.

  • Suction pipe couplings for two burners and one for returns.

Accessories and adaptations

  • 8 free relay outputs outlets

MODEL GPS-35 N GPS-70 N GPS-130 N GPS-200 N GPS-350 N GPS-950 N GPS-1500 N
FLOW l/h 30 70 130 200 350 950 1500
POWER SUPPLY VOLTS 230/400
mono phase
230/400
tri-phase (*)
230/400
tri-phase (*)
230/400
tri-phase (*)
230/400
tri-phase (*)
230/400
tri-phase
230/400
tri-phase
RECOMMENDED
SUCTION PIPE
MM Ø
(OD)
12 15 15 18 22 25 32
MOTOR
POWER
C.V. 1/6 1/4 1/3 1/3 1/3 3/4
KW 0,12 0,18 0,25 0,25 0,25 0,55 0,75
SUCTION BSP
THREAD
G 3/8”F G ½”F G ½”F G ¾”F G ¾”F G 1”F G 1 ¼” F
RETURN
PIPE BURNER
BSP
THREAD
G 3/8”F G ½”F G ½”F G ½”F G ¾”F G ¾”F G ¾”F
TANK
CAPACITY
lts. 24 68 68 68 238 238 245
MOTOR
PROTECTION
IP 20 55 55 55 55 55 55

- (*) There is a 230 single-phase version (W)