GP-M GE
Applications & Specific Features
- Multiple burner, appliances or service tanks supplied with one GP pressure unit.
- Appliances installed at different heights.
- Modulating burners when using the Inpro Oil Burner Inlet Assembly (see Datasheet).
- Oil Supply installation using ‘dead leg’ pipework. GP unit does not need external controls.
- GP units operate on an internal pressure switch only pumping fuel when required.
- Pressure regulators may be required at oil inlet to burners/appliances.
- Limited suction lift may require GP unit to be sited near the oil tank.
Accessories and adaptations Art. Nr.
-
Free voltage relay output to control from centralised Building Management System, in kit 3, 4 or 6 signals (2-thermal, motors 1 or 2 ON, low pressure and Leak safety ON).
-
GSM alarm system by SMS messages, or connection to modem. Adaptation of Pressure Group for high pressure, working conditions of up to 6 Kg/cm2
-
Leak collector trays with infrared detectors (standard in GP-800 and GP-1500).
-
Modifications to adapt to specifically regulated environments with tropicalised equipment or ATEX.
-
Solenoid valves with f
MODELO GP-70 N/GE GP-130 N/GE GP-200 N/GE GP-300 N/GE GP-500 N/GE GP-800 N/GE GP-1.500 N/GE FLOW l/h 70 130 200 300 500 800 1500 CONNECTION TO
THE HYDRAULIC
CIRCUIT
(Ø THREAD / Ø MM)SUCTION 1/2” F 1/2” F 1/2” F 3/4” F 3/4” F 1” F 1” F DRIVE 3/8” F 3/8” F 3/8” F 1/2” F 1/2” F 1/2” F 3/4” F POWER SUPPLY VOLTS 230/400
tri-phase*230/400
tri-phase*230/400
tri-phase*230/400
tri-phase*230/400
tri-phase230/400
tri-phase230/400
tri-phaseMOTOR
POWERC.V. 1/4 1/3 1/3 1/2 1/2 3/4 1½ KW 0,18 0,25 0,25 0,25 0,37 0,55 1,1 MAX.
PRESSUREKg/cm2 3,5 3,5 3,5 4 4 4 4 SAFETY VALVE
OPENS AT:Kg/cm2 4 4 4 4,5 4,5 4,5 4,5 MOTOR
PROTECTIONIP 55 55 55 55 55 55 55