ATAM and CAG+

TECHNICAL FEATURES

The CAG+ control system can manage 1, 2 or 3 filling areas depending on the configuration.
The display shows the level of daily tanks, the status of pumps, valves, etc… giving the possibility of performing either manual fillings or automatic
fillings, well as different maintenance tests, essential feature to have always those backup installation ready to enter into force.
It consists of a touch screen 5.7” monochrome with Mod Bus communication capability with SCADA. Color screen, TCP-IP communication protocol
are also available as additional requirement.

TECHNICAL SPECIFICATIONS

  • Voltage: 230 V

  • RCBO (Residual Current Breaker with Overcurrent): 40 A

  • MCB (Mains Circuit Breaker).: 40 A

  • Pump control (depending on project)

  • Maneuver (according to project)

  • Tanks control (according to project)

  • Solenoid (according to project)

MODEL FP 10 FP 23 FP 41 FP 90 FP 120 FP 240 FP 360 FP 570
MAX. FLOW l/h 180 300 450 700 900 1200 1500 2100
MOTOR
POWER
V 400 400 400 400 400 400 400 400
KW 0,25 0,25 0,25 0,33 0,55 0,55 0,55 1
MOTOR r.p.m 1400 1400 1400 1400 1400 1400 1400 1400
CONNECTION TO
THE HYDRAULIC
CIRCUIT
SUCTION 1/2” F 1/2” F 1/2” F 3/4” F 3/4” F 3/4” F 1” F 1” F
DRIVE 1/2” F 1/2” F 1/2” F 3/4” F 3/4” F 3/4” F 1” F 1” F
OVERPRESSURE 1/2” F 1/2” F 1/2” F 3/4” F 3/4” F 3/4” F 1” F 1” F
SECURITY VALVE
OPENS AT:
bar 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5
SOUND
LEVEL
dB (A) 58 58 58 58 58 58 58 58
MOTOR
PROTECTION
IP 55 55 55 55 55 55 55 55

- Produced and tested under DIN 12.514-1 standard